Support Center - Help topic

Home > Support Center > Search > Help Topic
I received a “The HMI system is being prohibited from accessing local devices. Please check if the HMI port no. (8000) is occupied” error.
Tags: Networking
The Offline or Online Simulator relies on an external process to run correctly, com_e30.exe. If this process is running before the Simulator begins, it can interfere with how the Simulator works, causing the Port 8000 error. If the Port 8000 error is being caused by another software using port 8000, you can change the port used by the Simulator.
Content Created by David Franzwa